Flare and relief systems: getting the basics right
Back to Knowledge Base
Process Safety 7 minKnowledge Base

Flare and relief systems: getting the basics right

2026-11-15

Relief valves protect equipment; the flare system protects everything downstream of them. Both have to be sized for the worst credible case, and both change whenever the plant does.

The situation

Relief and flare systems protect equipment from overpressure and dispose of released fluids safely. Design follows ISO 23251 / API 521 and covers relief scenarios, PSV sizing, back pressure, header hydraulics, knock-out drums, radiation and dispersion.

Two jobs

Relief devices stop equipment exceeding its design pressure. The flare system carries relieved gas and liquid safely away and burns it. A good design treats them as one system.

Diagram: Flare and relief systems
Figure: Atticus Energy, generic illustration.

Relief cases

Common cases include blocked outlets, fire, control valve failure, loss of cooling, tube rupture and power failure. Each device is sized for its governing case. The flare system is then sized for the worst credible combination of devices relieving together, typically from a single common cause such as power failure.

Key checks

  • Back pressure at each relief device, which affects capacity and the choice of valve type.
  • Velocity and noise in headers.
  • Liquid handling in the knock-out drum.
  • Low temperature from depressurisation, which can embrittle carbon steel.
  • Radiation and dispersion at grade and on nearby structures.

When the plant changes

New equipment, higher throughput, a new feed or a debottleneck can change relief loads. Every modification should trigger a check of affected relief cases and the flare system. This is one of the most common gaps found in brownfield plants.

Documentation

A current relief system register, with the governing case and basis for each device, makes reviews and audits far quicker and is essential for management of change.

Key Takeaways

  • Treat relief devices and the flare as one system.
  • Size for the worst credible common-cause scenario.
  • Check back pressure, low temperature and radiation.
  • Every modification can change relief loads; recheck them.

How Atticus helps

We review relief and flare systems, update relief registers, and assess the impact of debottlenecking and modifications on existing flare capacity.

Real-world examples

Documented incident

BP Texas City refinery — CSB investigation (2005)

At Texas City, hydrocarbons relieved into a blowdown drum with an atmospheric stack, not a flare, formed a flammable cloud. The CSB recommended replacing such atmospheric blowdown systems with properly designed flare systems.

Read the investigation / source
Documented incident

Williams Geismar olefins plant — CSB (2013)

At Williams Geismar, a reboiler isolated from its relief device was heated, over-pressurised and ruptured, killing two workers. Keeping a relief path open in every configuration is a fundamental design and operating requirement.

Read the investigation / source

If you get it wrong

  • Vessel rupture from inadequate or isolated relief.
  • Liquid carry-over to the flare tip, causing burning liquid rain-out.
  • Excessive radiation on personnel and equipment.
  • Header back pressure that stops PSVs from working as designed.

Relevant standards